Timer calculates the start duration
START_DUR
value, which indicates the
percentage ratio of the start situation and the set operating time. The value is available
in the Monitored data view.
The activation of the
BLOCK
input resets Timer and deactivates the
START
and
OPERATE
outputs.
Blocking logic
There are three operation modes in the blocking functionality. The operation modes
are controlled by the
BLOCK
input and the global setting
Configuration/System/
Blocking mode
which selects the blocking mode. The
BLOCK
input can be controlled
by a binary input, a horizontal communication input or an internal signal of the
protection relay's program. The influence of the
BLOCK
signal activation is
preselected with the global setting
Blocking mode
.
The
Blocking mode
setting has three blocking methods. In the "Freeze timers" mode,
the operation timer is frozen to the prevailing value. In the "Block all" mode, the whole
function is blocked and the timers are reset. In the "Block OPERATE output" mode,
the function operates normally but the
OPERATE
output is not activated.
4.3.1.5
Application
HIxPDIF provides a secure and dependable protection scheme against all types of
faults. The high-impedance principle is used for differential protection due to its
capability to manage the through-faults also with the heavy current transformer (CT)
saturation.
For current transformer recommendations, see the Requirements for
measurement transformers section in this manual.
High-impedance principle
The phase currents are measured from both the incoming and the outgoing feeder sides
of the busbar. The secondary of the current transformer in each phase is connected in
parallel with a protection relay measuring branch. Hence, the relay measures only the
difference of the currents. In an ideal situation, there is a differential current to operate
the relay only if there is a fault between the CTs, that is, inside the protected zone.
If there is a fault outside the zone, a high current, known as the through-fault current,
can go through the protected object. This can cause partial saturation in the CTs. The
relay operation is avoided with a stabilizing resistor (R
s
) in the protection relay
measuring branch. R
s
increases the impedance of the protection relay; hence the name
high-impedance differential scheme.
1MRS757454 D
Section 4
Protection functions
611 series
215
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......