operator can now restart the motor. A new emergency start cannot be made until the
10 minute time-out has passed or until the emergency start is released, whichever
takes longer.
The last change of the emergency start output signal is recorded.
5.4.6
Signals
Table 352:
ESMGAPC Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
ST_EMERG_RQ
BOOLEAN
0=False
Emergency start input
Table 353:
ESMGAPC Output signals
Name
Type
Description
ST_EMERG_ENA
BOOLEAN
Emergency start
5.4.7
Settings
Table 354:
ESMGAPC Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Motor standstill A
0.05...0.20
xIn
0.01
0.12
Current limit to check for motor standstill
condition
Table 355:
ESMGAPC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
5.4.8
Monitored data
Table 356:
ESMGAPC Monitored data
Name
Type
Values (Range)
Unit
Description
T_ST_EMERG
Timestamp
Emergency start
activation timestamp
ESMGAPC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Section 5
1MRS757454 D
Protection related functions
324
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......