4.6.7
Settings
Table 316:
FRPFRQ Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation mode
1=Freq<
2=Freq>
3=df/dt
4=Freq< + df/dt
5=Freq> + df/dt
6=Freq< OR df/dt
7=Freq> OR df/dt
1=Freq<
Frequency protection operation mode
selection
Start value Freq>
0.9000...1.2000
xFn
0.0001
1.0500
Frequency start value overfrequency
Start value Freq<
0.8000...1.1000
xFn
0.0001
0.9500
Frequency start value underfrequency
Start value df/dt
-0.2000...0.2000
xFn /s
0.0025
0.0100
Frequency start value rate of change
Operate Tm Freq
80...200000
ms
10
200
Operate delay time for frequency
Operate Tm df/dt
120...200000
ms
10
400
Operate delay time for frequency rate of
change
Table 317:
FRPFRQ Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 318:
FRPFRQ Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay Tm Freq
0...60000
ms
1
0
Reset delay time for frequency
Reset delay Tm df/dt
0...60000
ms
1
0
Reset delay time for rate of change
4.6.8
Monitored data
Table 319:
FRPFRQ Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Start duration
ST_DUR_OFRQ
FLOAT32
0.00...100.00
%
Start duration
ST_DUR_UFRQ
FLOAT32
0.00...100.00
%
Start duration
ST_DUR_FRG
FLOAT32
0.00...100.00
%
Start duration
FRPFRQ
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS757454 D
Section 4
Protection functions
611 series
287
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......