cable CAT 5e is used with the RJ-45 connector and an optical multi-mode cable (≤2
km) with the LC type connector.
In addition, communication modules with multiple Ethernet connectors enable the
forwarding of Ethernet traffic. These variants include an internal Ethernet switch that
handles the Ethernet traffic between an protection relay and a station bus. In this case,
the used network can be a ring or daisy-chain type of network topology. In loop type
topology, a self-healing Ethernet loop is closed by a managed switch supporting rapid
spanning tree protocol. In daisy-chain type of topology, the network is bus type and it
is either without switches, where the station bus starts from the station client, or with
a switch to connect some devices and the protection relays of this product series to the
same network.Internal Ethernet switch MAC table size is 512 entries. All Ethernet
ports share this one common MAC table.
Communication modules including Ethernet connectors X1, X2, and X3 can utilize
the third port for connecting any other device (for example, an SNTP server, that is
visible for the whole local subnet) to a station bus.
The protection relay's default IP address through rear Ethernet port is 192.168.2.10
with the TCP/IP protocol. The data transfer rate is 10 or 100 Mbps full duplex.
11.4.3
EIA-485 serial rear connection
The EIA-485 communication module follows the TIA/EIA-485 standard and is
intended to be used in a daisy-chain bus wiring scheme with 2-wire half-duplex or 4-
wire full-duplex, multi-point communication.
The maximum number of devices (nodes) connected to the bus where
the protection relay is used is 32, and the maximum length of the bus
is 1200 meters.
11.4.4
Communication interfaces and protocols
The communication protocols supported depend on the optional rear communication
module.
Table 482:
Supported station communication interfaces and protocols
Interfaces/protocols
Ethernet
Serial
100BASE-TX RJ-45
100BASE-FX LC
RS-485
IEC 61850
●
●
-
MODBUS RTU/ASCII
-
-
●
MODBUS TCP/IP
●
●
-
● = Supported
Section 11
1MRS757454 D
Protection relay's physical connections
504
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......