Table 128:
JAMPTOC Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
4.1.4.7
Settings
Table 129:
JAMPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Start value
0.10...10.00
xIn
0.01
2.50
Start value
Operate delay time
100...120000
ms
10
2000
Operate delay time
Table 130:
JAMPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
100
Reset delay time
4.1.4.8
Monitored data
Table 131:
JAMPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START
BOOLEAN
0=False
1=True
Start
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
JAMPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.1.4.9
Technical data
Table 132:
JAMPTOC Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±2 Hz
±1.5% of the set value or ±0.002 × I
n
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Section 4
1MRS757454 D
Protection functions
140
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......