detecting the risk of loss of synchronism than, for example, the lowest phase-to-phase
voltage.
Analyzing the loss of synchronism of a generator is rather complicated and requires a
model of the generator with its prime mover and controllers. The generator can be able
to operate synchronously even if the voltage drops by a few tens of percent for some
hundreds of milliseconds. The setting of PSPTUV is thus determined by the need to
protect the power station from the risks of the islanding conditions since that requires
a higher setting value.
The loss of synchronism of a generator means that the generator is unable to operate
as a generator with the network frequency but enters into an unstable condition in
which it operates by turns as a generator and a motor. Such a condition stresses the
generator thermally and mechanically. This kind of loss of synchronism should not be
mixed with the one between an island and the utility network. In the islanding
situation, the condition of the generator itself is normal but the phase angle and the
frequency of the phase-to-phase voltage can be different from the corresponding
voltage in the rest of the network. The island can have a frequency of its own relatively
fast when fed by a small power station with a low inertia.
PSPTUV complements other loss-of-grid protection principles based on the
frequency and voltage operation.
Motor stalling and failure to start can lead to a continuous undervoltage. The positive-
sequence undervoltage is used as a backup protection against the motor stall
condition.
4.5.5.6
Signals
Table 303:
PSPTUV Input signals
Name
Type
Default
Description
U
1
SIGNAL
0
Positive phase sequence voltage
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
Table 304:
PSPTUV Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
4.5.5.7
Settings
Table 305:
PSPTUV Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.010...1.200
xUn
0.001
0.500
Start value
Operate delay time
40...120000
ms
10
40
Operate delay time
1MRS757454 D
Section 4
Protection functions
611 series
279
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......