GUID-1A2BD0AD-B217-46F4-A6B4-6FC6E6256EB3 V2 EN
Figure 56:
Overcurrent protection of parallel lines using directional protection
relays
In these applications, there is a possibility that the fault current can also be fed from
the LV-side up to the HV-side. Therefore, the transformer is also equipped with
directional overcurrent protection.
GUID-74662396-1BAD-4AC2-ADB6-F4A8B3341860 V2 EN
Figure 57:
Overcurrent protection of parallel operating transformers
Closed ring network topology
The closed ring network topology is used in applications where electricity distribution
for the consumers is secured during network fault situations. The power is fed at least
from two directions which means that the current direction can be varied. The time
grading between the network level stages is challenging without unnecessary delays
in the time settings. In this case, it is practical to use the directional overcurrent
protection relays to achieve a selective protection scheme. Directional overcurrent
functions can be used in closed ring applications. The arrows define the operating
direction of the directional functionality. The double arrows define the non-
directional functionality where faults can be detected in both directions.
Section 4
1MRS757454 D
Protection functions
122
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......