GUID-63CA9A0F-24D8-4BA8-A667-88632DF53284 V1 EN
Figure 173:
Integral deadband supervision
The deadband value used in the integral calculation is configured with the
X deadband
setting. The value represents the percentage of the difference between the maximum
and minimum limit in the units of 0.001 percent x seconds.
The reporting delay of the integral algorithms in seconds is calculated with the
formula:
t s
deadband
Y
( )
(max min)
/
%
=
−
×
×
1000
100
∆
GUID-5381484E-E205-4548-A846-D3519578384B V1 EN
(Equation 34)
Example for CMMXU:
A deadband = 2500 (2.5% of the total measuring range of 40)
I_INST_A
=
I_DB_A
= 0.30
If
I_INST_A
changes to 0.40, the reporting delay is:
t s
s
( )
(
)
/
.
.
%
=
−
×
−
×
=
40
0
2500 1000
0 40
0 30
100
10
GUID-D1C387B1-4F2E-4A28-AFEA-431687DDF9FE V1 EN
Table 399:
Parameters for deadband calculation
Function
Settings
Maximum/minimum (=range)
Three-phase current
measurement (CMMXU)
A deadband
40/0 (=40xIn)
Three-phase voltage
measurement (VMMXU)
V Deadband
4/0 (=4xUn)
Residual current measurement
(RESCMMXU)
A deadband res
40/0 (=40xIn)
Residual voltage measurement
(RESVMMXU)
V deadband res
4/0 (=4xUn)
Table continues on next page
Section 7
1MRS757454 D
Measurement functions
356
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......