4.4.3.6
Signals
Table 250:
PREVPTOC Input signals
Name
Type
Default
Description
I
2
SIGNAL
0
Negative sequence current
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
Table 251:
PREVPTOC Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
4.4.3.7
Settings
Table 252:
PREVPTOC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.05...1.00
xIn
0.01
0.75
Start value
Operate delay time
100...60000
ms
10
100
Operate delay time
Table 253:
PREVPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
4.4.3.8
Monitored data
Table 254:
PREVPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
PREVPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS757454 D
Section 4
Protection functions
611 series
241
Technical Manual