Signals
Table 50:
TPGAPC Output signals
Name
Type
Description
OUT1
BOOLEAN
Output 1 status
OUT2
BOOLEAN
Output 2 status
Settings
Table 51:
TPGAPC Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Pulse time
0...60000
ms
1
150
Minimum pulse time
Technical revision history
Table 52:
TPGAPC Technical revision history
Technical revision
Change
B
Outputs now visible in menu
C
Internal improvement
3.14.1.2
Minimum pulse timer TPSGAPC
Function block
GUID-F9AACAF7-2183-4315-BE6F-CD53618009C0 V1 EN
Figure 32:
Function block
Functionality
The Minimum second pulse timer function TPSGAPC contains two independent
timers. The function has a settable pulse length (in seconds). The timers are used for
setting the minimum pulse length for example, the signal outputs. Once the input is
activated, the output is set for a specific duration using the
Pulse time
setting. Both
timers use the same setting parameter.
Section 3
1MRS757454 D
Basic functions
82
611 series
Technical Manual
Summary of Contents for Relion 611 Series