4.2.2.13
Technical data
Table 202:
DEFxPDEF Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±2 Hz
DEFLPDEF
Current:
±1.5% of the set value or ±0.002 × I
n
Voltage
±1.5% of the set value or ±0.002 × U
n
Phase angle:
±2°
DEFHPDEF
Current:
±1.5% of the set value or ±0.002 × I
n
(at currents in the range of 0.1…10 × I
n
)
±5.0% of the set value
(at currents in the range of 10…40 × I
n
)
Voltage:
±1.5% of the set value or ±0.002 × U
n
Phase angle:
±2°
Start time
1)2)
Minimum
Typical
Maximum
DEFHPDEF
I
Fault
= 2 × set
Start
value
42 ms
46 ms
49 ms
DEFLPDEF
I
Fault
= 2 × set
Start
value
58 ms
62 ms
66 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
1)
Measurement mode = default (depends on stage), current before fault = 0.0 × I
n
, f
n
= 50 Hz, earth-fault
current with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum
Start value = 2.5 × I
n
,
Start value multiples in range of 1.5...20
Section 4
1MRS757454 D
Protection functions
202
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......