DEL_INIT_2
•
DEL_INIT_3
•
DEL_INIT_4
DEL_INIT_2
and
INIT_2
are connected together with an OR-gate, as are inputs 3
and 4. Inputs 1, 5 and 6 do not have any delayed input. From the auto-reclosing point
of view, it does not matter whether
INIT_x
or
DEL_INIT_x
line is used for shot
initiation or blocking.
The auto-reclose function can also open the circuit breaker from any of the initiation
lines. It is selected with the
Tripping line
setting. As a default, all initiation lines
activate the
OPEN_CB
output.
A070276 V1 EN
Figure 213:
Simplified logic diagram of initiation lines
Each delayed initiation line has four different time settings:
Table 468:
Settings for delayed initiation lines
Setting name
Description and purpose
Str x delay shot 1
Time delay for the
DEL_INIT_x
line, where x is
the number of the line 2, 3 or 4. Used for shot 1.
Str x delay shot 2
Time delay for the
DEL_INIT_x
line, used for shot
2.
Str x delay shot 3
Time delay for the
DEL_INIT_x
line, used for shot
3.
Str x delay shot 4
Time delay for the
DEL_INIT_x
line, used for
shots 4 and 5. Optionally, can also be used with
SOTF.
1MRS757454 D
Section 8
Control functions
611 series
431
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......