frequency in a power system indicates that the generated power is too low to meet the
demands of the load connected to the power grid.
The underfrequency can occur as a result of the overload of generators operating in an
isolated system. It can also occur as a result of a serious fault in the power system due
to the deficit of generation when compared to the load. This can happen due to a fault
in the grid system on the transmission lines that link two parts of the system. As a
result, the system splits into two with one part having the excess load and the other part
the corresponding deficit.
The frequency gradient is applicable in all the situations where the change of the
fundamental power system voltage frequency should be detected reliably. The
frequency gradient can be used for both increasing and decreasing the frequencies.
This function provides an output signal suitable for load shedding, generator
shedding, generator boosting, set point change in sub-transmission DC systems and
gas turbine startup. The frequency gradient is often used in combination with a low
frequency signal, especially in smaller power systems where the loss of a large
generator requires quick remedial actions to secure the power system integrity. In such
situations, the load shedding actions are required at a rather high frequency level.
However, in combination with a large negative frequency gradient, the
underfrequency protection can be used at a high setting.
4.6.6
Signals
Table 314:
FRPFRQ Input signals
Name
Type
Default
Description
F
SIGNAL
0
Measured frequency
dF/dt
SIGNAL
0
Rate of change of frequency
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
Table 315:
FRPFRQ Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
OPR_UFRQ
BOOLEAN
Operate signal for underfrequency
OPR_OFRQ
BOOLEAN
Operate signal for overfrequency
OPR_FRG
BOOLEAN
Operate signal for frequency gradient
START
BOOLEAN
Start
ST_UFRQ
BOOLEAN
Start signal for underfrequency
ST_OFRQ
BOOLEAN
Start signal for overfrequency
ST_FRG
BOOLEAN
Start signal for frequency gradient
Section 4
1MRS757454 D
Protection functions
286
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......