A070874 V1 EN
Figure 203:
Initiation after elapsed discrimination time - new shot begins
8.2.4.5
Sequence controller
When the
LOCKED
output is active, the AR function is in lockout. This means that new
sequences cannot be initialized, because AR is insensitive to initiation commands. It
can be released from the lockout state in the following ways.
•
The function is reset through communication with the
RecRs
parameter. The
same functionality can also be found in the Clear menu (DARREC1 reset).
•
The lockout is automatically reset after the reclaim time, if the
Auto lockout reset
setting is in use.
If the
Auto lockout reset
setting is not in use, the lockout can be
released only with the
RecRs
parameter.
The AR function can go to lockout for many reasons.
•
The
INHIBIT_RECL
input is active.
•
All shots have been executed and a new initiation is made (final trip).
•
The time set with the
Auto wait time
parameter expires and the automatic
sequence initiation is not allowed because of a synchronization failure.
•
The time set with the
Wait close time
parameter expires, that is, the circuit breaker
does not close or the automatic sequence initiation is not allowed due to a closing
failure of the circuit breaker.
•
A new shot is initiated during the discrimination time.
•
The time set with the
Max wait time
parameter expires, that is, the master unit
does not release the slave unit.
1MRS757454 D
Section 8
Control functions
611 series
417
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......