Table 23:
COM2 serial communication settings
Parameter
Values (Range)
Unit
Step
Default
Description
Fiber mode
0=No fiber
2=Fiber optic
0=No fiber
Fiber mode
Serial mode
1=RS485 2Wire
2=RS485 4Wire
3=RS232 no
handshake
4=RS232 with
handshake
1=RS485 2Wire
Serial mode
CTS delay
0...60000
ms
1
0
CTS delay
RTS delay
0...60000
ms
1
0
RTS delay
Baudrate
1=300
2=600
3=1200
4=2400
5=4800
6=9600
7=19200
8=38400
9=57600
10=115200
6=9600
Baudrate
3.2
Self-supervision
The protection relay's extensive self-supervision system continuously supervises the
software and the electronics. It handles run-time fault situation and informs the user
about a fault via the LHMI and through the communication channels.
There are two types of fault indications.
•
Internal faults
•
Warnings
3.2.1
Internal faults
When an internal relay fault is detected, relay protection operation is disabled, the
green Ready LED begins to flash and the self-supervision output contact is activated.
Internal fault indications have the highest priority on the LHMI. None
of the other LHMI indications can override the internal fault
indication.
An indication about the fault is shown as a message on the LHMI. The text
Internal Fault
with an additional text message, a code, date and time, is shown
to indicate the fault type.
1MRS757454 D
Section 3
Basic functions
611 series
45
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......