7.1.5.3
Signals
Table 408:
VMMXU Input signals
Name
Type
Default
Description
U_A_AB
SIGNAL
0
Phase to earth voltage A or phase to phase voltage
AB
U_B_BC
SIGNAL
0
Phase to earth voltage B or phase to phase voltage
BC
U_C_CA
SIGNAL
0
Phase to earth voltage C or phase to phase voltage
CA
BLOCK
BOOLEAN
0=False
Block signal for all binary outputs
Table 409:
VMMXU Output signals
Name
Type
Description
HIGH_ALARM
BOOLEAN
High alarm
HIGH_WARN
BOOLEAN
High warning
LOW_WARN
BOOLEAN
Low warning
LOW_ALARM
BOOLEAN
Low alarm
7.1.5.4
Settings
Table 410:
VMMXU Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Num of phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases required by limit
supervision
V high high limit
0.00...4.00
xUn
1
1.40
High alarm voltage limit
V high limit
0.00...4.00
xUn
1
1.20
High warning voltage limit
V low limit
0.00...4.00
xUn
1
0.00
Low warning voltage limit
V low low limit
0.00...4.00
xUn
1
0.00
Low alarm voltage limit
V deadband
100...100000
1
10000
Deadband configuration value for integral
calculation. (percentage of difference
between min and max as 0,001 % s)
Table 411:
VMMXU Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement mode
1=RMS
2=DFT
2=DFT
Selects used measurement mode
Section 7
1MRS757454 D
Measurement functions
364
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......