the accumulated operation time exceeds the set limits. It utilizes a binary input to
indicate the active operation condition.
The accumulated operation time is one of the parameters for scheduling a service on
the equipment like motors. It indicates the use of the machine and hence the
mechanical wear and tear. Generally, the equipment manufacturers provide a
maintenance schedule based on the number of hours of service.
6.3.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The
corresponding parameter values are "On" and "Off".
The operation of MDSOPT can be described using a module diagram. All the modules
in the diagram are explained in the next sections.
GUID-6BE6D1E3-F3FB-45D9-8D6F-A44752C1477C V1 EN
Figure 171:
Functional module diagram
Operation time counter
This module counts the operation time. When
POS_ACTIVE
is active, the count is
continuously added to the time duration until it is deactivated. At any time the
OPR_TIME
output is the total duration for which
POS_ACTIVE
is active. The unit of
time duration count for
OPR_TIME
is hour. The value is available through the
Monitored data view.
The
OPR_TIME
output is a continuously increasing value and it is stored in a non-
volatile memory. When
POS_ACTIVE
is active, the
OPR_TIME
count starts
increasing from the previous value. The count of
OPR_TIME
saturates at the final
value of 299999, that is, no further increment is possible. The activation of
RESET
can
reset the count to the
Initial value
setting.
Limit Supervision
This module compares the motor run-time count to the set values of
Warning value
and
Alarm value
to generate the
WARNING
and
ALARM
outputs respectively when the
counts exceed the levels.
The activation of the
WARNING
and
ALARM
outputs depends on the
Operating time
mode
setting. Both
WARNING
and
ALARM
occur immediately after the conditions are
met if
Operating time mode
is set to “Immediate”. If
Operating time mode
is set to
“Timed Warn”,
WARNING
is activated within the next 24 hours at the time of the day
set using the
Operating time hour
setting. If
Operating time mode
is set to “Timed
1MRS757454 D
Section 6
Supervision functions
611 series
347
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......