Characteristic
Value
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
P-to-P+backup: No suppression
1)
Measurement mode = default (depends on stage), current before fault = 0.0 × I
n
, f
n
= 50 Hz, fault current
in one phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum
Start value = 2.5 × I
n
,
Start value multiples in range of 1.5...20
4.1.1.12
Technical revision history
Table 91:
PHIPTOC Technical revision history
Technical revision
Change
B
Minimum and default values changed to 40 ms for
the
Operate delay time setting
C
Minimum and default values changed to 20 ms for
the
Operate delay time setting
Minimum value changed to 1.00 x I
n
for the
Start
value setting
D
Internal improvement
E
Internal improvement
Table 92:
PHHPTOC Technical revision history
Technical revision
Change
C
Measurement mode "P-to-P + backup" replaced
with "Peak-to-Peak"
D
Step value changed from 0.05 to 0.01 for the
Time
multiplier setting
E
Internal improvement
F
Internal improvement
Table 93:
PHLPTOC Technical revision history
Technical revision
Change
B
Minimum and default values changed to 40 ms for
the
Operate delay time setting
C
Step value changed from 0.05 to 0.01 for the
Time
multiplier setting
D
Internal improvement
E
Internal improvement
Section 4
1MRS757454 D
Protection functions
106
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......