•
The frequent operation counter limit is reached and new sequence is initiated. The
lockout is released when the recovery timer elapses.
•
The protection trip signal has been active longer than the time set with the
Max
wait time
parameter since the shot initiation.
•
The circuit breaker is closed manually during an autoreclosing sequence and the
manual close mode is FALSE.
8.2.4.6
Protection coordination controller
The
PROT_CRD
output is used for controlling the protection functions. In several
applications, such as fuse-saving applications involving down-stream fuses, tripping
and initiation of shot 1 should be fast (instantaneous or short-time delayed). The
tripping and initiation of shots 2, 3 and definite tripping time should be delayed.
In this example, two overcurrent elements PHLPTOC and PHIPTOC are used.
PHIPTOC is given an instantaneous characteristic and PHLPTOC is given a time
delay.
The
PROT_CRD
output is activated, if the
SHOT_PTR
value is the same or higher than
the value defined with the
Protection crd limit
setting and all initialization signals
have been reset. The
PROT_CRD
output is reset under the following conditions:
•
If the cut-out time elapses
•
If the reclaim time elapses and the AR function is ready for a new sequence
•
If the AR function is in lockout or disabled, that is, if the value of the
Protection
crd mode
setting is "AR inoperative" or "AR inop, CB man".
The
PROT_CRD
output can also be controlled with the
Protection crd mode
setting.
The setting has the following modes:
•
"no condition": the
PROT_CRD
output is controlled only with the
Protection crd
limit
setting
•
"AR inoperative": the
PROT_CRD
output is active, if the AR function is disabled
or in the lockout state, or if the
INHIBIT_RECL
input is active
•
"CB close manual": the
PROT_CRD
output is active for the reclaim time if the
circuit breaker has been manually closed, that is, the AR function has not issued
a close command
•
"AR inop, CB man": both the modes "AR inoperative" and "CB close manual" are
effective
•
"always": the
PROT_CRD
output is constantly active
Section 8
1MRS757454 D
Control functions
418
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......