GUID-6E9DC0FE-7457-4317-9480-8CCC6D63AB35 V2 EN
(Equation 47)
t[s] operate time in seconds
A
the set value of
Curve parameter A
B
the set value of
Curve parameter B
C
the set value of
Curve parameter C
D
the set value of
Curve parameter D
E
the set value of
Curve parameter E
U
measured voltage
U> the set value of
Start value
k
the set value of
Time multiplier
9.3.1.3
IDMT curve saturation of overvoltage protection
For the overvoltage IDMT mode of operation, the integration of the operate time does
not start until the voltage exceeds the value of
Start value
. To cope with discontinuity
characteristics of the curve, a specific parameter for saturating the equation to a fixed
value is created. The
Curve Sat Relative
setting is the parameter and it is given in
percents compared to
Start value
. For example, due to the curve equation B and C, the
characteristics equation output is saturated in such a way that when the input voltages
are in the range of
Start value
to
Curve Sat Relative
in percent over
Start value
, the
equation uses
Start value
* (1.0 +
Curve Sat Relative
/ 100 ) for the measured voltage.
Although, the curve A has no discontinuities when the ratio U/U> exceeds the unity,
Curve Sat Relative
is also set for it. The
Curve Sat Relative
setting for curves A, B and
C is 2.0 percent. However, it should be noted that the user must carefully calculate the
curve characteristics concerning the discontinuities in the curve when the
programmable curve equation is used. Thus, the
Curve Sat Relative
parameter gives
another degree of freedom to move the inverse curve on the voltage ratio axis and it
effectively sets the maximum operate time for the IDMT curve because for the voltage
ratio values affecting by this setting, the operation time is fixed, that is, the definite
time, depending on the parameters but no longer the voltage.
9.3.2
IDMT curves for undervoltage protection
In the inverse-time modes, the operate time depends on the momentary value of the
voltage, the lower the voltage, the faster the operate time. The operate time calculation
or integration starts immediately when the voltage goes below the set value of the
Start
value
setting and the
START
output is activated.
The
OPERATE
output of the component is activated when the cumulative sum of the
integrator calculating the undervoltage situation exceeds the value set by the inverse-
Section 9
1MRS757454 D
General function block features
482
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......