For the IDMT curves, it is possible to define minimum and maximum operate times
with the
Minimum operate time
and
Maximum operate time
settings. The
Machine
time Mult
setting parameter corresponds to the machine constant, equal to the I
2
2
t
constant of the machine, as stated by the machine manufacturer. In case there is a
mismatch between the used CT and the protected motor's nominal current values, it is
possible to fit the IDMT curves for the protected motor using the
Current reference
setting.
The activation of the
OPERATE
output activates the
BLK_RESTART
output. The
deactivation of the
OPERATE
output activates the cooling timer. The timer is set to the
value entered in the
Cooling time
setting. The
BLK_RESTART
output is kept active
until the cooling timer is exceeded. If the negative-sequence current increases above
the set value during this period, the
OPERATE
output is activated immediately.
The
T_ENARESTART
output indicates the duration for which the
BLK_RESTART
output remains active, that is, it indicates the remaining time of the cooling timer. The
value is available in the monitored data view.
The timer calculates the start duration value START_DUR, which indicates the
percentage ratio of the start situation and the set operation time. The value is available
in the monitored data view.
4.4.4.5
Timer characteristics
MNSPTOC supports both DT and IDMT characteristics. The DT timer characteristics
can be selected with "ANSI Def. Time" or "IEC Def. Time" in the
Operating curve
type
setting. The functionality is identical in both cases. When the DT characteristics
are selected, the functionality is only affected by the
Operate delay time
and
Reset
delay time
settings.
The protection relay provides two user-programmable IDMT characteristics curves,
"Inv. curve A" and "Inv. curve B".
Current-based inverse definite minimum time curve (IDMT)
In inverse-time modes, the operate time depends on the momentary value of the
current: the higher the current, the shorter the operate time. The operate time
calculation or integration starts immediately when the current exceeds the set
Start
value
and the
START
output is activated.
The
OPERATE
output of the component is activated when the cumulative sum of the
integrator calculating the overcurrent situation exceeds the value set by the inverse
time mode. The set value depends on the selected curve type and the setting values
used.
The
Minimum operate time
and
Maximum operate time
settings define the minimum
operate time and maximum operate time possible for the IDMT mode. For setting
these parameters, a careful study of the particular IDMT curves is recommended.
Section 4
1MRS757454 D
Protection functions
244
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......