3.16.1.2
Functionality
Redundant Ethernet channel supervision RCHLCCH represents LAN A and LAN B
redundant Ethernet channels.
3.16.1.3
Signals
Table 60:
RCHLCCH output signals
Parameter
Values (Range) Unit
Step
Default Description
CHLIV
True
False
Status of redundant Ethernet channel
LAN A. When
Redundant mode is set to
"HSR" or "PRP", value is "True" if the
protection relay is receiving redundancy
supervision frames. Otherwise value is
"False".
REDCHLIV
True
False
Status of redundant Ethernet channel
LAN B. When
Redundant mode is set to
"HSR" or "PRP", value is "True" if the
protection relay is receiving redundancy
supervision frames. Otherwise value is
"False".
LNKLIV
Up
Down
Link status of redundant port LAN A.
Valid only when
Redundant mode is set
to "HSR" or "PRP".
REDLNKLIV
Up
Down
Link status of redundant port LAN B.
Valid only when
Redundant mode is set
to "HSR" or "PRP".
3.16.1.4
Settings
Table 61:
Redundancy settings
Parameter
Values (Range) Unit
Step
Default Description
Redundant
mode
None
PRP
HSR
None
Mode selection for Ethernet switch on
redundant communication modules.
The "None" mode is used with normal
and Self-healing Ethernet topologies.
3.16.1.5
Monitored data
Monitored data is available in four locations.
•
Monitoring/Communication/Ethernet/Activity/CHLIV_A
•
Monitoring/Communication/Ethernet/Activity/REDCHLIV_B
•
Monitoring/Communication/Ethernet/Link statuses/LNKLIV_A
•
Monitoring/Communication/Ethernet/Link statuses/REDLNKLIV_B
Section 3
1MRS757454 D
Basic functions
86
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......