delay setting can even be as high as within the range of seconds, for example
around 30 seconds.
The activation of the
BLOCK
input signal deactivates the
MOT_START
output.
Thermal stress calculator
Because of the high current surges during the start-up period, a thermal stress is
imposed on the rotor. With less air circulation in the ventilation of the rotor before it
reaches its full speed, the situation becomes even worse. Consequently, a long start-
up causes a rapid heating of the rotor.
This module calculates the thermal stress developed in the motor during start-up. The
heat developed during the starting can be calculated with the equation.
W
R
i
t dt
s
s
t
=
( )
∫
2
0
GUID-7A92209F-7451-415B-8C3D-276A6ED4A44B V1 EN
(Equation 29)
R
s
combined rotor and stator resistance
i
s
starting current of the motor
t
starting time of the motor
This equation is normally represented as the integral of I²t. It is a commonly used
method in protective protection relays to protect the motor from thermal stress during
starting. The advantage of this method over the traditional definite time overcurrent
protection is that when the motor is started with a reduced voltage as in the star-delta
starting method, the starting current is lower. This allows more starting time for the
motor since the module is monitoring the integral of I²t.
The module calculates the accumulated heat continuously and compares it to the
limiting value obtained from the product of the square of the values of the
Motor start-
up A
and
Motor start-up time
settings. When the calculated value of the thermal stress
exceeds this limit, the
OPR_IIT
output is activated.
The module also measures the time
START_TIME
required by the motor to attain the
rated speed and the relative thermal stress
IIT_RL
. The values are available in the
Monitored data view.
The activation of the
BLOCK
input signal resets the thermal stress calculator and
deactivates the
OPR_IIT
output.
Stall protection
This module is activated only when the selected
Operation mode
setting value is "IIt
& stall" or "IIt & stall, CB".
1MRS757454 D
Section 4
Protection functions
611 series
293
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......