7.1.8
Frequency measurement FMMXU
7.1.8.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Frequency measurement
FMMXU
f
f
7.1.8.2
Function block
GUID-5CCF8F8C-E1F4-421B-8BE9-C0620F7446A7 V2 EN
Figure 179:
Function block
7.1.8.3
Functionality
The frequency measurement range is 35...75 Hz. The estimated frequencies outside
the measurement range are considered to be out of range and the minimum and
maximum values are then shown.
When the frequencies cannot be measured, for example, due to too low voltage
amplitude, the default value for frequency measurement can be selected with the
Def
frequency Sel
setting parameter. In the “Nominal” mode the frequency is set to 50 Hz
(or 60 Hz) and in “Zero” mode the frequency is set to zero and shown in parentheses.
7.1.8.4
Signals
Table 429:
FMMXU Input signals
Name
Type
Default
Description
F
SIGNAL
-
Measured system frequency
7.1.8.5
Settings
Table 430:
FMMXU Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
F high high limit
35.00...75.00
Hz
1
60.00
High alarm frequency limit
F high limit
35.00...75.00
Hz
1
55.00
High warning frequency limit
F low limit
35.00...75.00
Hz
1
45.00
Low warning frequency limit
F low low limit
35.00...75.00
Hz
1
40.00
Low alarm frequency limit
F deadband
100...100000
1
1000
Deadband configuration value for integral
calculation (percentage of difference
between min and max as 0,001 % s)
Section 7
1MRS757454 D
Measurement functions
372
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......