Table 404:
CMMXU Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement mode
1=RMS
2=DFT
2=DFT
Selects used measurement mode
7.1.4.5
Monitored data
Table 405:
CMMXU Monitored data
Name
Type
Values (Range)
Unit
Description
IL1-A
FLOAT32
0.00...40.00
xIn
Measured current
amplitude phase A
IL2-A
FLOAT32
0.00...40.00
xIn
Measured current
amplitude phase B
IL3-A
FLOAT32
0.00...40.00
xIn
Measured current
amplitude phase C
Max demand IL1
FLOAT32
0.00...40.00
xIn
Maximum demand for
Phase A
Max demand IL2
FLOAT32
0.00...40.00
xIn
Maximum demand for
Phase B
Max demand IL3
FLOAT32
0.00...40.00
xIn
Maximum demand for
Phase C
Min demand IL1
FLOAT32
0.00...40.00
xIn
Minimum demand for
Phase A
Min demand IL2
FLOAT32
0.00...40.00
xIn
Minimum demand for
Phase B
Min demand IL3
FLOAT32
0.00...40.00
xIn
Minimum demand for
Phase C
Time max demand
IL1
Timestamp
Time of maximum
demand phase A
Time max demand
IL2
Timestamp
Time of maximum
demand phase B
Time max demand
IL3
Timestamp
Time of maximum
demand phase C
Time min demand
IL1
Timestamp
Time of minimum
demand phase A
Time min demand
IL2
Timestamp
Time of minimum
demand phase B
Time min demand
IL3
Timestamp
Time of minimum
demand phase C
BLOCK
BOOLEAN
0=False
1=True
Block signal for all binary
outputs
HIGH_ALARM
BOOLEAN
0=False
1=True
High alarm
HIGH_WARN
BOOLEAN
0=False
1=True
High warning
LOW_WARN
BOOLEAN
0=False
1=True
Low warning
Table continues on next page
1MRS757454 D
Section 7
Measurement functions
611 series
361
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......