4.3.1.2
Function block
GUID-A8C4ADB7-8892-422F-8B00-873C47A66A3E V1 EN
Figure 98:
Function block
4.3.1.3
Functionality
The high-impedance differential protection function HIxPDIF is a general differential
protection. It provides a phase-segregated short circuit protection for the busbar.
However, the function can also be used for providing generator, motor, transformer
and reactor protection.
The function starts and operates when the differential current exceeds the set limit.
The operate time characteristics are according to definite time (DT).
The function contains a blocking functionality. It is possible to block the function
outputs, timer or the whole function.
4.3.1.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The
corresponding parameter values are "On" and "Off".
The operation of HIxPDIF can be described with a module diagram. All the modules
in the diagram are explained in the next sections.
1MRS757454 D
Section 4
Protection functions
611 series
213
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......