Each LED is seen in the Application Configuration tool as an individual function
block. Each LED has user-editable description text for event description. The state
("None", "OK", "Alarm") of each LED can also be read under a common monitored
data view for programmable LEDs.
The LED status also provides a means for resetting the individual LED via
communication. The LED can also be reset from configuration with the
RESET
input.
The resetting and clearing function for all LEDs is under the
Clear
menu.
The menu structure for the programmable LEDs is presented in
common color selection setting
Alarm colour
for all
ALARM
inputs is in the
General
menu, while the LED-specific settings are under the LED-specific menu nodes.
Alarm mode
Description
LED 1
Programmable LEDs
Alarm color
Red
Green
Follow-S
Follow-F
Latched-S
LatchedAck-F-S
Programmable LED description
LED 2
General
GUID-0DED5640-4F67-4112-9A54-E8CAADFFE547 V1 EN
Figure 13:
Menu structure
Alarm mode alternatives
The
ALARM
input behavior can be selected with the alarm mode settings from the
alternatives "Follow-S", "Follow-F", "Latched-S" and "LatchedAck-F-S". The
OK
input behavior is always according to "Follow-S". The alarm input latched modes can
be cleared with the reset input in the application logic.
GUID-58B6C3F2-873A-4B13-9834-9BB21FCA5704 V1 EN
Figure 14:
Symbols used in the sequence diagrams
"Follow-S": Follow Signal, ON
In this mode
ALARM
follows the input signal value, Non-latched.
1MRS757454 D
Section 3
Basic functions
611 series
51
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......