7.1.7.2
Function block
A070779 V2 EN
Figure 178:
Function block
7.1.7.3
Signals
Table 422:
RESVMMXU Input signals
Name
Type
Default
Description
Uo
SIGNAL
0
Residual voltage
BLOCK
BOOLEAN
0=False
Block signal for all binary outputs
Table 423:
RESVMMXU Output signals
Name
Type
Description
HIGH_ALARM
BOOLEAN
High alarm
HIGH_WARN
BOOLEAN
High warning
7.1.7.4
Settings
Table 424:
RESVMMXU Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
V Hi high limit res
0.00...4.00
xUn
1
0.20
High alarm voltage limit
V high limit res
0.00...4.00
xUn
1
0.05
High warning voltage limit
V deadband res
100...100000
1
10000
Deadband configuration value for integral
calculation. (percentage of difference
between min and max as 0,001 % s)
Table 425:
RESVMMXU Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement mode
1=RMS
2=DFT
2=DFT
Selects used measurement mode
Section 7
1MRS757454 D
Measurement functions
370
611 series
Technical Manual