Characteristic
Value
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1) Residual voltage before fault = 0.0 × U
n
, f
n
= 50 Hz, residual voltage with nominal frequency injected
from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
4.5.3.10
Technical revision history
Table 294:
ROVPTOV Technical revision history
Technical revision
Change
B
Added a setting parameter for the "Measured Uo"
or "Calculated Uo" selection
C
Internal improvement
D
Internal improvement
4.5.4
Negative-sequence overvoltage protection NSPTOV
4.5.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Negative-sequence overvoltage
protection
NSPTOV
U2>
47O-
4.5.4.2
Function block
GUID-F94BCCE8-841F-405C-B659-3EF26F959557 V1 EN
Figure 128:
Function block
4.5.4.3
Functionality
The negative-sequence overvoltage protection function NSPTOV is used to detect
negative sequence overvoltage conditions. NSPTOV is used for the protection of
machines.
The function starts when the negative sequence voltage exceeds the set limit.
NSPTOV operates with the definite time (DT) characteristics.
The function contains a blocking functionality. It is possible to block function outputs,
the definite timer or the function itself, if desired.
Section 4
1MRS757454 D
Protection functions
272
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......