Table 296:
NSPTOV Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
4.5.4.7
Settings
Table 297:
NSPTOV Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.010...1.000
xUn
0.001
0.030
Start value
Operate delay time
40...120000
ms
1
40
Operate delay time
Table 298:
NSPTOV Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 299:
NSPTOV Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
4.5.4.8
Monitored data
Table 300:
NSPTOV Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
NSPTOV
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS757454 D