Table 168:
EFHPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Minimum operate time
20...60000
ms
1
20
Minimum operate time for IDMT curves
Reset delay time
0...60000
ms
1
20
Reset delay time
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used measurement mode
Io signal Sel
1=Measured Io
2=Calculated Io
1=Measured Io
Selection for used Io signal
Table 169:
EFIPTOC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
1.00...40.00
xIn
0.01
1.00
Start value
Start value Mult
0.8...10.0
0.1
1.0
Multiplier for scaling the start value
Operate delay time
20...200000
ms
10
20
Operate delay time
Table 170:
EFIPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 171:
EFIPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
Io signal Sel
1=Measured Io
2=Calculated Io
1=Measured Io
Selection for used Io signal
4.2.1.10
Monitored data
Table 172:
EFLPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
EFLPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS757454 D
Section 4
Protection functions
611 series
169
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......