4.2.1.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The
corresponding parameter values are "On" and "Off".
The operation of EFxPTOC can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
A070437 V3 EN
Figure 73:
Functional module diagram
Level detector
The operating quantity can be selected with the setting
Io signal Sel
. The selectable
options are "Measured Io" and "Calculated Io". The operating quantity is compared to
the set
Start value
. If the measured value exceeds the set
Start value
, the level detector
sends an enable-signal to the timer module. If the
ENA_MULT
input is active, the
Start
value
setting is multiplied by the
Start value Mult
setting.
The protection relay does not accept the
Start value
or
Start value Mult
setting if the product of these settings exceeds the
Start value
setting
range.
The start value multiplication is normally done when the inrush detection function
(INRPHAR) is connected to the
ENA_MULT
input.
Timer
Once activated, the timer activates the
START
output. Depending on the value of the
Operating curve type
setting, the time characteristics are according to DT or IDMT.
When the operation timer has reached the value of
Operate delay time
in the DT mode
or the maximum value defined by the inverse time curve, the
OPERATE
output is
activated.
When the user-programmable IDMT curve is selected, the operation time
characteristics are defined by the parameters
Curve parameter A
,
Curve parameter B
,
Curve parameter C
,
Curve parameter D
and
Curve parameter E
.
If a drop-off situation happens, that is, a fault suddenly disappears before the operate
delay is exceeded, the timer reset state is activated. The functionality of the timer in
the reset state depends on the combination of the
Operating curve type
,
Type of reset
curve
and
Reset delay time
settings. When the DT characteristic is selected, the reset
Section 4
1MRS757454 D
Protection functions
162
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......