Group
Jumper connection
Description
Notes
X7
1-2
B- bias enabled
COM2
4-wire RX channel
2-3
B- bias disabled
1)
X8
1-2
A+ bias enabled
2-3
A+ bias disabled
1)
X9
1-2
Bus termination
enabled
2-3
Bus termination
disabled
1)
1) Default setting
It is recommended to enable biasing only at one end of the bus.
Termination is enabled at each end of the bus.
It is recommended to ground the signal directly to earth from one node
and through capacitor from other nodes.
The optional communication modules include support for EIA-485 serial
communication (X5 connector). Depending on the configuration, the communication
modules can host either two 2-wire-ports or one 4-wire-port.
The two 2-wire ports are called COM1 and COM2. Alternatively, if there is only one
4-wire port configured, the port is called COM2.
Table 488:
EIA-485 connections for COM0001-COM0003
Pin
2-wire mode
4-wire mode
10
COM1
A/+
COM2
Rx/+
9
B/-
Rx/-
8
COM2
A/+
Tx/+
7
B/-
Tx/-
6
AGND (isolated ground)
5
IRIG-B +
4
IRIG-B -
3
-
2
GNDC (case via capacitor)
1
GND (case)
Section 11
1MRS757454 D
Protection relay's physical connections
508
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......