coil in compensated networks. As a result the characteristic angle is set automatically
to suit the earthing method used. The RCA_CTL input can be used to change the
operation criteria as described in
Table 181:
Relay characteristic angle control in Iosin(φ) and Iocos(φ) operation criteria
Operation mode setting:
RCA_CTL
= FALSE
RCA_CTL
= TRUE
Iosin
Actual operation mode: Iosin
Actual operation mode: Iocos
Iocos
Actual operation mode: Iocos
Actual operation mode: Iosin
Table 182:
Characteristic angle control in phase angle operation mode
Characteristic angle setting
RCA_CTL
= FALSE
RCA_CTL
= TRUE
-90°
φ
RCA
= -90°
φ
RCA
= 0°
0°
φ
RCA
= 0°
φ
RCA
= -90°
Use of the extended phase angle characteristic
The traditional method of adapting the directional earth-fault protection function to
the prevailing neutral earthing conditions is done with the
Characteristic angle
setting. In an unearthed network,
Characteristic angle
is set to -90 degrees and in a
compensated network
Characteristic angle
is set to 0 degrees. In case the earthing
method of the network is temporarily changed from compensated to unearthed due to
the disconnection of the arc suppression coil, the
Characteristic angle
setting should
be modified correspondingly. This can be done using the setting groups or the
RCA_CTL
input. Alternatively, the operating sector of the directional earth-fault
protection function can be extended to cover the operating sectors of both neutral
earthing principles. Such characteristic is valid for both unearthed and compensated
network and does not require any modification in case the neutral earthing changes
temporarily from the unearthed to compensated network or vice versa.
The extended phase angle characteristic is created by entering a value of over 90
degrees for the
Min forward angle
setting; a typical value is 170 degrees (
Min reverse
angle
in case
Directional mode
is set to "Reverse"). The
Max forward angle
setting
should be set to cover the possible measurement inaccuracies of current and voltage
transformers; a typical value is 80 degrees (
Max reverse angle
in case
Directional
mode
is set to "Reverse").
1MRS757454 D
Section 4
Protection functions
611 series
183
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......