Section 6
Supervision functions
6.1
Trip circuit supervision TCSSCBR
6.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Trip circuit supervision
TCSSCBR
TCS
TCM
6.1.2
Function block
A070788 V1 EN
Figure 158:
Function block
6.1.3
Functionality
The trip circuit supervision function TCSSCBR is designed to supervise the control
circuit of the circuit breaker. The invalidity of a control circuit is detected by using a
dedicated output contact that contains the supervision functionality. The failure of a
circuit is reported to the corresponding function block in the relay configuration.
The function starts and operates when TCSSCBR detects a trip circuit failure. The
operating time characteristic for the function is DT. The function operates after a
predefined operating time and resets when the fault disappears.
The function contains a blocking functionality. Blocking deactivates the
ALARM
output and resets the timer.
6.1.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The
corresponding parameter values are "On" and "Off".
The operation of TCSSCBR can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
1MRS757454 D
Section 6
Supervision functions
611 series
329
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......