Table 173:
EFHPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
EFHPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 174:
EFIPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
EFIPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.2.1.11
Technical data
Table 175:
EFxPTOC Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±2 Hz
EFLPTOC
±1.5% of the set value or ±0.002 × I
n
EFHPTOC
and
EFIPTOC
±1.5% of set value or ±0.002 × I
n
(at currents in the range of 0.1…10 × I
n
)
±5.0% of the set value
(at currents in the range of 10…40 × I
n
)
Start time
1)2)
Minimum
Typical
Maximum
EFIPTOC:
I
Fault
= 2 × set
Start
value
I
Fault
= 10 × set
Start
value
16 ms
11 ms
19 ms
12 ms
23 ms
14 ms
EFHPTOC and
EFLPTOC:
I
Fault
= 2 × set
Start
value
23 ms
26 ms
29 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Table continues on next page
Section 4
1MRS757454 D
Protection functions
170
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......