Table 459:
CBXCBR Output signals
Name
Type
Description
SELECTED
BOOLEAN
Object selected
EXE_OP
BOOLEAN
Executes the command for open direction
EXE_CL
BOOLEAN
Executes the command for close direction
OP_REQ
BOOLEAN
Open request
CL_REQ
BOOLEAN
Close request
OPENPOS
BOOLEAN
Signal for open position of apparatus from I/O
CLOSEPOS
BOOLEAN
Signal for close position of apparatus from I/O
OKPOS
BOOLEAN
Apparatus position is ok
OPEN_ENAD
BOOLEAN
Opening is enabled based on the input status
CLOSE_ENAD
BOOLEAN
Closing is enabled based on the input status
8.1.7
Settings
Table 460:
CBXCBR Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation mode on/off
Select timeout
10000...300000
ms
10000
30000
Select timeout in ms
Pulse length
10...60000
ms
1
200
Open and close pulse length
Control model
0=status-only
1=direct-with-
normal-security
4=sbo-with-
enhanced-security
4=sbo-with-
enhanced-security
Select control model
Operation timeout
10...60000
ms
1
500
Timeout for negative termination
Identification
CBXCBR1 switch
position
Control Object identification
Table 461:
CBXCBR Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation counter
0...10000
1
0
Breaker operation cycles
Adaptive pulse
0=False
1=True
1=True
Stop in right position
Event delay
0...10000
ms
1
200
Event delay of the intermediate position
Vendor
0
External equipment vendor
Serial number
0
External equipment serial number
Model
0
External equipment model
Section 8
1MRS757454 D
Control functions
402
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......