A070870 V1 EN
Figure 206:
Logic diagram of auto-initiation sequence detection
Automatic initiation can be selected with the
Auto initiation Cnd
setting to be the
following:
•
Not allowed: no automatic initiation is allowed
•
When the synchronization fails, the automatic initiation is carried out when the
auto wait time elapses and the reclosing is prevented due to a failure during the
synchronism check
•
When the circuit breaker does not close, the automatic initiation is carried out if
the circuit breaker does not close within the wait close time after issuing the
reclose command
•
Both: the automatic initiation is allowed when synchronization fails or the circuit
breaker does not close.
1MRS757454 D
Section 8
Control functions
611 series
425