Table 504:
Insulation tests
Description
Type test value
Reference
Dielectric tests
2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min,
communication
IEC 60255-27
Impulse voltage test
5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J,
communication
IEC 60255-27
Insulation resistance
measurements
>100 MΩ, 500 V DC
IEC 60255-27
Protective bonding resistance
<0.1 Ω, 4 A, 60 s
IEC 60255-27
Table 505:
Mechanical tests
Description
Requirement
Reference
Vibration tests (sinusoidal)
Class 2
IEC 60068-2-6 (test Fc)
IEC 60255-21-1
Shock and bump test
Class 2
IEC 60068-2-27 (test Ea shock)
IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2
Seismic test
Class 2
IEC 60255-21-3
Table 506:
Environmental tests
Description
Type test value
Reference
Dry heat test
•
96 h at +55ºC
•
16 h at +85ºC
1)
IEC 60068-2-2
Dry cold test
•
96 h at -25ºC
•
16 h at -40ºC
IEC 60068-2-1
Damp heat test
•
6 cycles (12 h + 12 h) at
+25°C…+55°C, humidity
>93%
IEC 60068-2-30
Change of temperature test
•
5 cycles (3 h + 3 h)
at -25°C...+55°C
IEC60068-2-14
Storage test
•
96 h at -40ºC
•
96 h at +85ºC
IEC 60068-2-1
IEC 60068-2-2
1) For relays with an LC communication interface the maximum operating temperature is +70
o
C
Table 507:
Product safety
Description
Reference
LV directive
2006/95/EC
Standard
EN 60255-27 (2013)
EN 60255-1 (2009)
1MRS757454 D
Section 13
Protection relay and functionality tests
611 series
519
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......