GUID-D8F15382-5E3F-4371-B2AD-936D72941803 V1 EN
Figure 104:
Secondary waveform of a saturated CT
The secondary circuit voltage can easily exceed the isolation voltage of the CTs,
connection wires and the protection relay because of the stabilizing resistance and CT
saturation. A voltage dependent resistor (VDR, R
u
) is used to limit the voltage as
shown in
Busbar protection scheme
The basic concept for any bus differential protection relay is a direct use of Kirchoff’s
first law that the sum of all currents connected to one differential protection zone is
zero. If the sum is not zero, an internal fault has occurred. In other words, as seen by
the busbar differential protection, the sum of all currents that flow into the protection
zone, that is, currents with positive value, must be equal to currents that flow out of the
protection zone, that is, currents with negative value, at any instant of time.
shows an example of a phase segregated single busbar protection
employing high-impedance differential protection. The example system consists of a
single incoming busbar feeder and two outgoing busbar feeders. The CTs from both
the outgoing busbar feeders and the incoming busbar feeders are connected in parallel
with the polarity. During normal load conditions, the total instantaneous incoming
current is equal to the total instantaneous outgoing current and the difference current
is negligible. A fault in the busbar results in an imbalance between the incoming and
the outgoing current. The difference current flows through the protection relay, which
generates a trip signal.
1MRS757454 D
Section 4
Protection functions
611 series
219
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......