Table 491:
Energizing inputs
Description
Value
Rated frequency
50/60 Hz
Current inputs
Rated current, I
n
0.2/1 A
1)
1/5 A
2)
Thermal withstand
capability:
•
Continuously
4 A
20 A
•
For 1 s
100 A
500 A
Dynamic current
withstand:
•
Half-wave value
250 A
1250 A
Input impedance
<100 mΩ
<20 mΩ
Voltage inputs
Rated voltage
60...210 V AC
Voltage withstand:
•
Continuous
240 V AC
•
For 10 s
360 V AC
Burden at rated voltage <0.05 VA
1) Ordering option for residual current input
2) Residual current and/or phase current
Table 492:
Binary inputs
Description
Value
Operating range
±20% of the rated voltage
Rated voltage
24...250 V DC
Current drain
1.6...1.9 mA
Power consumption
31.0...570.0 mW
Threshold voltage
16...176 V DC
Reaction time
<3 ms
Table 493:
Signal output X100: SO1
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
5 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time
constant L/R<40 ms, at 48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load
100 mA at 24 V AC/DC
Section 12
1MRS757454 D
Technical data
512
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......