3.12.2.3
Signal outputs SO1, SO2 and SO3 in BIO0006
The optional card BIO0006 provides the signal outputs SO1, SO2 and SO3. Signal
outputs SO1 and SO2 are dual, parallel form C contacts; SO3 is a single form C
contact.
10
12
11
13
15
14
X130
SO1
SO2
16
18
17
SO3
GUID-C5B5FD1C-617B-4F38-A0D4-D98735E69530 V1 EN
Figure 27:
Signal output in BIO0006
3.13
GOOSE function blocks
GOOSE function blocks are used for connecting incoming GOOSE data to
application. They support BOOLEAN, Dbpos, Enum, FLOAT32, INT8 and INT32
data types.
Common signals
The VALID output indicates the validity of received GOOSE data, which means in
case of valid, that the GOOSE communication is working and received data quality
bits (if configured) indicate good process data. Invalid status is caused either by bad
data quality bits or GOOSE communication failure. See IEC 61850 engineering guide
for details.
The OUT output passes the received GOOSE value for the application. Default value
(0) is used if VALID output indicates invalid status. The IN input is defined in the
GOOSE configuration and can always be seen in SMT sheet.
1MRS757454 D
Section 3
Basic functions
611 series
79
Technical Manual