Table 431:
FMMXU Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Def frequency Sel
1=Nominal
2=Zero
1=Nominal
Default frequency selection
7.1.8.6
Monitored data
Table 432:
FMMXU Monitored data
Name
Type
Values (Range)
Unit
Description
f-Hz
FLOAT32
35.00...75.00
Hz
Measured frequency
F_INST
FLOAT32
35.00...75.00
Hz
Frequency,
instantaneous value
F_DB
FLOAT32
35.00...75.00
Hz
Frequency, reported
value
F_RANGE
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
Measured frequency
range
7.1.8.7
Technical data
Table 433:
FMMXU Technical data
Characteristic
Value
Operation accuracy
±10 mHz
(in measurement range 35...75 Hz)
7.1.8.8
Technical revision history
Table 434:
FMMXU Technical revision history
Technical revision
Change
B
Added new setting
Def frequency Sel. Frequency
measurement range lowered from 35 Hz to 10 Hz.
7.1.9
Sequence current measurement CSMSQI
7.1.9.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Sequence current measurement
CSMSQI
I1, I2, I0
I1, I2, I0
1MRS757454 D
Section 7
Measurement functions
611 series
373
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......