Table 83:
PHHPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Minimum operate time
20...60000
ms
1
20
Minimum operate time for IDMT curves
Reset delay time
0...60000
ms
1
20
Reset delay time
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used measurement mode
Table 84:
PHIPTOC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
1.00...40.00
xIn
0.01
1.00
Start value
Start value Mult
0.8...10.0
0.1
1.0
Multiplier for scaling the start value
Operate delay time
20...200000
ms
10
20
Operate delay time
Table 85:
PHIPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Num of start phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases required for operate
activation
Table 86:
PHIPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
4.1.1.10
Monitored data
Table 87:
PHLPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
PHLPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Section 4
1MRS757454 D
Protection functions
104
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......