IEC 61850
remote
IED
IEC 61850
remote
REMOTE
LOCAL
OFF
IEC 61850
remote
IED
IEC 61850
remote
IEC 61850
remote
IEC 61850
remote
IED
GUID-08BACCE4-AF4A-4150-A01A-49FBEE63B438 V1 EN
Figure 20:
Station authority is “L,R”
The present control status can be monitored in the HMI or PCM600 via
MonitoringControl command
with the
LR state
parameter or from the IEC 61850
data object CTRL.LLN0. LocKeyHMI.
Table 41:
Station authority level “L,R” using R/L button
L/R control
L/R control status
Control access
R/L button
CTRL.LLN0.LocSta
CTRL.LLN0.MltLev
L/R state
CTRL.LLN0.LocKeyHMI
Local user
IEC 61850 client
1)
Local
N/A
FALSE
1
x
Remote
N/A
FALSE
2
x
Off
N/A
FALSE
0
1) Client IEC 61850 command originator category check is not performed.
3.9
Fault recorder FLTRFRC
3.9.1
Function block
GUID-6BE3D723-0C52-4047-AA41-73D7C828B02B V1 EN
Figure 21:
Function block
3.9.2
Functionality
The protection relay has the capacity to store the records of 128 latest fault events.
Fault records include fundamental or RMS current values. The records enable the user
to analyze recent power system events. Each fault record (FLTRFRC) is marked with
an up-counting fault number and a time stamp that is taken from the beginning of the
fault.
The fault recording period begins from the start event of any protection function and
ends if any protection function trips or the start is restored before the operate event. If
1MRS757454 D
Section 3
Basic functions
611 series
63
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......