4.5.3.7
Settings
Table 289:
ROVPTOV Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.010...1.000
xUn
0.001
0.030
Residual overvoltage start value
Operate delay time
40...300000
ms
1
40
Operate delay time
Table 290:
ROVPTOV Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Uo signal Sel
1=Measured Uo
2=Calculated Uo
1=Measured Uo
Selection for used Uo signal
Table 291:
ROVPTOV Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
4.5.3.8
Monitored data
Table 292:
ROVPTOV Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
ROVPTOV
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.5.3.9
Technical data
Table 293:
ROVPTOV Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
voltage: f
n
±2 Hz
±1.5% of the set value or ±0.002 × U
n
Start time
1)2)
Minimum
Typical
Maximum
U
Fault
= 2 × set
Start
value
48 ms
51 ms
54 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Table continues on next page
1MRS757454 D
Section 4
Protection functions
611 series
271
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......