4.6.9
Technical data
Table 320:
FRPFRQ Technical data
Characteristic
Value
Operation accuracy
f>/f<
±5 mHz
df/dt
±50 mHz/s (in range |df/dt| <5 Hz/s)
±2.0% of the set value (in range 5 Hz/s < |df/dt| <
15 Hz/s)
Start time
f>/f<
<80 ms
df/dt
<120 ms
Reset time
<150 ms
Operate time accuracy
±1.0% of the set value or ±30 ms
4.6.10
Technical revision history
Table 321:
FRPFRQ Technical revision history
Technical revision
Change
B
Step value changed from 0.001 to 0.0001 for the
Start value Freq> and Start value Freq< settings.
C
df/dt setting step changed from 0.005 ×Fn /s to
0.0025 ×Fn /s.
D
Internal improvement.
4.7
Motor start-up supervision STTPMSU
4.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Motor start-up supervision
STTPMSU
Is2t n<
49,66,48,51LR
4.7.2
Function block
GUID-A37CF63B-5273-423B-9DC3-AACADB668AEE V2 EN
Figure 134:
Function block
Section 4
1MRS757454 D
Protection functions
288
611 series
Technical Manual
Summary of Contents for Relion 611 Series