First reclose time
= 1.0s
•
Init signals CBB1
= 7 (three lowest bits: 111000 = 7)
•
Blk signals CBB1
= 16 (the fifth bit: 000010 = 16)
•
Shot number CBB1
= 1
CBB2 settings are:
•
Second reclose time
= 10s
•
Init signals CBB2
= 6 (the second and third bits: 011000 = 6)
•
Blk signals CBB2
= 16 (the fifth bit: 000010 = 16)
•
Shot number CBB2
= 2
CBB3 settings are:
•
Third reclose time
= 30s
•
Init signals CBB3
= 4 (the third bit: 001000 = 4)
•
Blk signals CBB3
= 16 (the fifth bit: 000010 = 16)
•
Shot number CBB3
= 3
CBB4 settings are:
•
Fourth reclose time
= 0.5s
•
Init signals CBB4
= 8 (the fourth bit: 000100 = 8)
•
Blk signals CBB4
= 0 (no blocking signals related to this CBB)
•
Shot number CBB4
= 1
If a shot is initiated from the
INIT_1
line, only one shot is allowed before lockout.
If a shot is initiated from the
INIT_3
line, three shots are allowed before lockout.
A sequence initiation from the
INIT_4
line leads to a lockout after two shots. In a
situation where the initiation is made from both the
INIT_3
and
INIT_4
lines, a
third shot is allowed, that is, CBB3 is allowed to start. This is called conditional
lockout. If the initiation is made from the
INIT_2
and
INIT_3
lines, an immediate
lockout occurs.
The
INIT_5
line is used for blocking purposes. If the
INIT_5
line is active during
a sequence start, the reclose attempt is blocked and the AR function goes to lockout.
If more than one CBBs are started with the shot pointer, the CBB with
the smallest individual number is always selected. For example, if the
INIT_2
and
INIT_4
lines are active for the second shot, that is, the
shot pointer is 2, CBB2 is started instead of CBB5.
Even if the initiation signals are not received from the protection functions, the AR
function can be set to continue from the second to the fifth reclose shot. The AR
function can, for example, be requested to automatically continue with the sequence
when the circuit breaker fails to close when requested. In such a case, the AR function
Section 8
1MRS757454 D
Control functions
412
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......