GUID-F0214060-11E8-42F7-B3B9-AF5AC08A1079 V1 EN
Figure 118:
MNSPTOC Inverse Curve A
If the negative sequence current drops below the
Start value
setting, the reset time is
defined as:
t s
a
b
[ ]
=
×
100
GUID-8BE4B6AC-FB61-4D30-B77B-3E599D5BAE81 V1 EN
(Equation 27)
t[s] Reset time in seconds
a
set
Cooling time
b
percentage of start time elapse (
START_DUR
)
Section 4
1MRS757454 D
Protection functions
246
611 series
Technical Manual