1
2
3
4
5
5
GUID-13DA5833-D263-4E23-B666-CF38B1011A4B V1 EN
Figure 22:
Binary input filtering
1 t
0
2 t
1
3 Input signal
4 Filtered input signal
5 Filter time
At the beginning, the input signal is at the high state, the short low state is filtered and
no input state change is detected. The low state starting from the time t
0
exceeds the
filter time, which means that the change in the input state is detected and the time tag
attached to the input change is t
0
. The high state starting from t
1
is detected and the
time tag t
1
is attached.
Each binary input has a filter time parameter "Input # filter", where # is the number of
the binary input of the module in question (for example "Input 1 filter").
Table 45:
Input filter parameter values
Parameter
Values
Default
Input # filter time
5...1000 ms
5 ms
3.11.2
Binary input inversion
The parameter
Input # invert
is used to invert a binary input.
Table 46:
Binary input states
Control voltage
Input # invert
State of binary input
No
0
FALSE (0)
Yes
0
TRUE (1)
No
1
TRUE (1)
Yes
1
FALSE (0)
Section 3
1MRS757454 D
Basic functions
74
611 series
Technical Manual
Summary of Contents for Relion 611 Series
Page 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Page 2: ......
Page 22: ...16 ...
Page 30: ...24 ...
Page 308: ...302 ...
Page 400: ...394 ...
Page 506: ...500 ...
Page 516: ...510 ...
Page 522: ...516 ...
Page 528: ...522 ...
Page 533: ...527 ...
Page 534: ......
Page 535: ......